| Sl No |
Description |
Technical specification and Display parameter |
| 1 |
Application |
3phase 4 wire(20-100A) |
| 2 |
Rated voltage |
voltage,3X230, Phase to neutral |
| 3 |
Rated current |
20-100A |
| 4 |
Frequency |
50± 5% |
| 5 |
Overload capacity |
120% of Ib |
| 6 |
Minimum starting currentin % of base
current |
0.1% of Ib |
| 7 |
Accuracy class |
1 |
| 8 |
Details of case |
polycarbonate(seamless ultrasonic welding with
transperent meter top cover |
| 9 |
Standard to which the meter confirm |
AS per IS 13779: 1999 |
| 10 |
Type of energy Registration mechanism |
Backlid LCD Display |
| 11 |
MD Reset mechanism |
1.Automatic on 24:00 hours of the last day of the month 2.Manual Reset |
| 12 |
Working range |
|
| |
Voltage |
(-)50% to (+)20% of rated voltage |
| |
Current |
0.1% to 120% of Ib |
| 13 |
Type of load(linear,nonlinear,balanced/unbalanced at any p.f) |
All types of load |
| 14 |
Display Details(Descriptive in order of
display) |
1) Display test |
| |
|
2)Real time and date |
| |
|
3)Rising demand with elapsed time |
| |
|
4)Active energy(import) |
| |
|
5)Reactive Energy |
| |
|
6)Apparent Energy |
| |
|
7)Max Demand KW |
| |
|
8)Max Demand KVA |
| |
|
9)M.D. Reset count |
| |
|
10)Instantneous power factor with sign lag/lead |
| |
|
11)Instantneous frequency |
| |
|
12)Instantneous Voltage (phase wise) |
| |
|
13)Instantneous Current( Phase wise) |
| |
|
14)instantneous active load(KW) |
| |
|
15)instantneus reactive load |
| |
|
16)inatantneus apparent load |
| |
|
17)billing power on hours |
| |
|
18)TOD Energy |
| |
|
19)TOD max Demand In KVA |
| |
|
20)Cumulative max demand |
| |
|
21)present status of temper |
| |
|
22)latest occurrence of Abnormality with date
&time |
| |
|
23)latest restoration of abnormality with date &
time |
| 15 |
i)process of display(Automatic in
cyclicmanner/through push botton |
1)Automatic in cyclic manner(No
1,2,3,4,5,6,7,8,9,2)through push botton
|
| |
ii) Digits |
8(Eight) digits |
| |
iii) Period of display for each parameter |
8(eight) Seconds |
| 16 |
Memory |
non volatile memory without battery back up at
least 12 years
|
| 17 |
Non volatile memory |
Sufficient to store data(MD &energy) of
consecutive12 biiling period in addition to tamper
details8 TOD Zones,tamper information as
described in detailed technical specification |
| 18 |
Tamper data preservation capacity |
Able to store at least 200
events(occurrence&restoration as separate
events) with roll over facility
|
| 19 |
load survey capability |
|
| |
a) Parameter logged |
KW import,KVA |
| |
b) Logging interval |
30 minutes |
| |
No of days load survey |
70 days at interval of 30 minutes |
| 20 |
earthing terminals |
AS per IS 13779:1999 |
| 21 |
Time of the zone |
zone-1- 7am to 10am |
| |
|
zone-2- 10am to 18pm |
| |
|
zone-3-18pm tp22pm |
| |
|
zone-4-22pm to 6am |
| |
|
zone -5- 6am to 7 am |
| 22 |
Capability for fraud prevention&
detection
|
The meter stores in its memory occurrence and
restoration the following tampers with date &time
and also log of the event |
| |
|
Missing potential |
| |
|
CT short/Ct open/td>
|
| |
|
Current reversal |
| |
|
Neutral Disturbance |
| |
|
Magnatic influence |
| 23 |
Sealing and locking arrangement |
2 sealing screws on the meter cover& 2 sealing
screw on terminal cover are provided.Separate
sealing arrangement are provided for MD reset
button& optical port
|
| 24 |
Type of communication |
Data can be transferred to and fro from aCmRI
conforming to CBIP-111 through optical port
conforming to IEC-1107 provided in front of the
meter.data can also be transferred through central
based computer using GSPMS lines and suitable
modems.The data element size and its overhead
speed of transmission should less than 10
minutes. |
| 25 |
Others |
Meter should record energy correctly |
| |
|
i) in case of Current reversal |
| |
|
II)In case of neutral fail |
| |
|
iii)In case of neutral disturbance |
| |
|
iv) Meter should record at Imax in any tamper
event due to magnatic influence |
| 26 |
Real time Clock |
Time drift of Real time clock in the meteris less
than±7 minutes per years |