Specification of Single Phase 2 wire static energy meter of class of 1.0 accuracy
Sl No Description Technical specification and Display parameter
1 Standards IS:13779,IEC 1036 & CBIP technical reportNo 88 and its latest amendments
2 Voltage 240 volts(P-N), +20% to - 40% V ref,However the meter should withstand and maximum system voltage i.e. 440 volts
3 Rating 5-30A, 10-60A
4 Display LCD(six digits)
5 MD Registration Meter shall store MD every 15 minutes period along with date 7 time. At the end of every 15 minutes,new MD shall be previous MD and store which ever is higher and the same shall be displayed.
6 Test out put device flashing LED visible from the front
7 Body of the meter a) Top transparent and base opaque material polycarbonate of LEXAN 143A/943AA or equivalent grade b) Front cover and base should be ultrasonically welded C) Top cover should be designed so as the internal component should not be visible
8 Terminal block

made of polycarbonate of grade 500R or equivalent brass or copper current terminals with flat head brass crews

9 Terminal cover transparent materials cover with provision of dealing through sealings screws
10 Diagram of connection Diagram of external connection to be shown on terminal cover
11 Marking on the name plate meter should be clearly visible ,indelible,and distingly name plate marked in acordance with IS specifications
  c)variation in voltage AS per IS: 14697:1999
10 Accuracy class 0.2s
11 Total weight of the case <2kg
12 Details of case polycarbonate(seamless ultrasonic welding with transperent meter top cover)
13 HV withstand 4kv as per IS 14697:1999 cause 12.7.6.3
14 Insulation resistance As per 14697:1999
15 Standard to which the meter conferm AS per IS 14697: 1999
16 Type of energy Registration mechanism Backlid LCD Display
17 MD Reset mechanism 1.Automatic on 24:00 hours of the last day of the month 2.manual Reset
18 Insulation test As per 14697:1999
19 Temparature co-efficient from 10% of rated load(5deg.C to 45deg.C) As per 14697:1999
20 Working range  
  voltage (-)50% to (+)20% of rated voltage
  current 0.1% to 120% of Ib
21 Type of load(linear,non linear,balanced/unbalanced at any p.f) All types of load
22 Display Details(Descriptive in order of display) 1) Display test
    real time and date
    rising demand with elapsed time
    active energy
    reactive energy( both lag &lead)
    apparent energy
    Maximum Demand(both KW & KVA)
    MD reset count
    Instantenuous power factor with sign for lag &lead
    Instantenuous frequency
    Instantenuous voltage( phase wise)
    Instantenuous current(phase wise)
    Instantenuous Activeload
    Instantenuous reactive load(withsign for lag/lead)
    Instantenuous apparent load
    Billing power on hours
    TODenergie
    TOD Max demand in kva
    Cumulative max demand
    present status of temper
   > latest occurrence of Abnormality with date &time
    latest restoration of abnormality with date & time
  ii)process of display(Automatic in cyclicmanner/through push botton 1)Automatic in cyclic manner(No 1,2,3,4,5,6,7,8,9) 2)through push botton
  iii) Digits 8(Eight) digits
  iv)Segments for display of one digit 7(seven)
  iv) Period of display for each parameter 12(twelve) Seconds
23 Memory non volatile memory without battery back up at least 12 years
24 Non volatile memory Sufficient to store data(MD &energy) of consecutive12 biiling period in addition to tamper details7 TOD Zones,tamper information as described in detailed technical specification
25 Meter can power up by means of external battery in absence of supply voltage meter can be powered up by means of internal battery in absence of supply voltage
26 Tamper data preservation capacity Able to store at least 200 events(occurrence&restoration as separate events with roll over facility
27 Multiplying factor(if meter is used for different voltage) CT ratio and PT ratio is programmable for direct reading from the meter,However if purchaser requires,he may also use a multiplication factor without programming CT ratio and PT Ratio.
28 load survey capability  
  a) Parameter logged KW import,KVA
  b) Logging interval 15 minutes
  c)no of days load survey 70 days at interval of 15 minutes
29 Earthing terminals AS per IS 14697:1999
30 Time of the zone zone-1- 7am to 10am
    zone-2- 10am to 18pm
    zone-3-18pm tp22pm
    zone-4-22pm to 6am
    zone -5- 6am to 7 am
31 Capability for fraud prevention& detection The meter stores in its memory occurrence and restoration the following tampers with date &time and also log of the event
    Missing potential
    CT short/Ct open
    Current reversal
    current unbalance
    current missing
32 Sealing and locking arrangement 2 sealing screws on the meter cover& 2 sealing screw on terminal cover are provided.Separate sealing arrangement are provided for MD reset button& optical port
33

Type of communication

data can be transferred to and fro from aCmRI conforming to CBIP-111 through optical port conforming to IEC-1107 provided in front of the meter.data can also be transferred through central based computer using GSPMS lines and suitable modems.The data element size and its overhead speed of transmission should less than 10 minutes
  Others meter should record energy correctly
    i) in case of Current reversal
    II)In case of neutral fail
    iii)In case of neutral disturbance
    iv) meter should record at Imax in any tamper event due to magnatic influence
34 Real time Clock Time drift of Real time clock in the meteris less than±7 minutes per years
 
 