| Sl No |
Description |
Technical specification and Display parameter |
| 1 |
Application |
3 phase 4wire, CT, PT operated |
| 2 |
rated voltage |
-/230 (Phase to neutral) |
| 3 |
rated current |
-/5 A( basic Current) |
| 4 |
frequency |
50± 5% |
| 5 |
overload capacity |
120% of Ib |
| 6 |
Minimum starting currentin % of base current |
0.1% of Ib |
| 7 |
loss of potential circuit |
AS per IS: 14697:1999 |
| |
loss of current circuit |
AS per IS: 14697:1999 |
| |
Change in error due to |
AS per IS: 14697:1999 |
| |
a) variation in frequency |
AS per IS: 14697:1999 |
| |
b) variation in temparature |
AS per IS: 14697:1999 |
| |
c)variation in voltage |
AS per IS: 14697:1999 |
| 8 |
Accuracy class |
0.5s |
| 9 |
total weight of the case |
< 2kg |
| 10 |
details of case |
Polycarbonate(seamless ultrasonic welding with transperent meter top cover) |
| 11 |
HV withstand |
4kv as per IS 14697:1999 cause 12.7.6.3 |
| 12 |
Insulation resistance |
As per 14697:1999 |
| 13 |
Standard to which the meter conferm |
AS per IS 14697:1999 |
| 14 |
Type of energy Registration mechanism |
Backlid LCD Display |
| 15 |
MD Reset mechanism |
1.Automatic on 24:00 hours of the last day of the month
2.manual Reset |
| 16 |
Insulation test |
As per 14697:1999 |
| 17 |
Temparature co-efficient from 10% of rated load(5deg.C to 45deg.C) |
As per 14697:1999 |
| 18 |
Working range |
|
| |
voltage |
(-)50% to (+)20% of rated voltage |
| |
current |
0.1% to 120% of Ib |
| 19 |
type of load(linear,non linear,balanced/unbalanced at any p.f) |
All types of load |
| 20 |
Display Details(Descriptive in order of display) |
1) Display test |
| |
|
Real time and date |
| |
|
Rising demand with elapsed time |
| |
|
Active energy |
| |
|
Reactive energy (both lag &lead) |
| |
|
Apparent energy |
| |
|
Maximum Demand(both KW & KVA) |
| |
|
MD reset count |
| |
|
Instantenuous power factor with sign for lag &lead |
| |
|
Instantenuous frequency |
| |
|
Instantenuous voltage (phase wise) |
| |
|
Instantenuous current(phase wise) |
| |
|
Instantenuous Activeload |
| |
|
Instantenuous reactive load (withsign for lag/lead) |
| |
|
Instantenuous apparent load |
| |
|
Billing power on hours |
| |
|
TODenergies |
| |
|
TOD Max demand in kva |
| |
|
Cumulative max demand |
| |
|
Present status of temper |
| |
|
latest occurrence of Abnormality with date &time |
| |
|
latest restoration of abnormality with date & time |
| 21 |
ii)process of display(Automatic in
cyclicmanner/through push botton
|
1)Automatic in cyclic manner(No
1,2,3,4,5,6,7,8,9)
2)through push botton |
| |
iii) Digits |
8(Eight) digits |
| |
iv)Segments for display of one digit |
7(seven) |
| |
iv) period of display for each parameter |
12(twelve) Seconds |
| 22 |
Memory |
atnon volatile memory without battery back up at least 12 years
|
| 23 |
Non volatile memory |
Sufficient to store data(MD &energy) of
consecutive12 biiling period in addition to tamper
details7 TOD Zones,tamper information as
described in detailed technical specification |
| 24 |
meter can power up by means of
external battery in absence of supply
voltage |
meter can be powered up by means of internal
battery in absence of supply voltage |
| 25 |
tamper data preservation capacity |
Able to store at least 200
events(occurrence&restoration as separate
events) with roll over facility |
| 26 |
load survey capability |
|
| |
a) Parameter logged |
KW import,KVA |
| |
b) Logging interval |
15 minutes |
| |
c)no of days load survey |
70 days at interval of 15 minutes |
| 27 |
earthing terminals |
AS per IS 14697:1999 |
| 28 |
Time of the zone |
zone-1- 7am to 10am |
| |
|
zone-2- 10am to 18pm |
| |
|
zone-3-18pm tp22pm |
| |
|
zone-4-22pm to 6am |
| |
|
zone -5- 6am to 7 am |
| 29 |
capability for fraud prevention&
detection
|
The meter stores in its memory occurrence and
restoration the following tampers with date &time
and also log of the event |
| |
|
Missing potential |
| |
|
CT short/Ct open |
| |
|
CT short/Ct open |
| |
|
Current unbalance |
| |
|
Current missing |
| 30 |
Sealing and locking arrangement |
2 sealing screws on the meter cover& 2 sealing
screw on terminal cover are provided.Separate
sealing arrangement are provided for MD reset
button& optical port |
| 31 |
Type of communication |
Data can be transferred to and fro from aCmRI
conforming to CBIP-111 through optical port
conforming to IEC-1107 provided in front of the
meter.data can also be transferred through
central based computer using GSPMS lines and
suitable modems.The data element size and its
overhead speed of transmission should less than
10 minutes. |
| 32 |
Others |
Meter should record energy correctly |
| |
|
i) in case of Current reversal |
| |
|
II)In case of neutral fail |
| |
|
iii)In case of neutral disturbance |
| |
|
iv) Meter should record at Imax in any tamper
event due to magnatic influence |
| 33 |
Real time Clock |
Time drift of Real time clock in the meteris less
than±7 minutes per years |